20個電氣元件選型口訣

發布日期:2022-09-02 09:39:22   來源:行業動態   瀏覽量:

Part.1

已知三相電(dian)動機容量,求其額定電(dian)流

口訣:

容量除以(yi)千(qian)伏數(shu),商乘系(xi)數(shu)點七(qi)六。

三(san)相(xiang)二百二電機,千瓦三(san)點五安培。

常用三百八電機,一個千(qian)瓦兩安培。

低壓六百六電機,千瓦(wa)一點二安培(pei)。

高壓三(san)千伏電機,四個千瓦一安培。

高壓六千伏電機,八個(ge)千瓦一安培(pei)。

容量大一點(dian)的減一點(dian),小(xiao)一點(dian)的加一點(dian)

 

精確計算電流I=P/U×√3×cosφ(A)

補充:準(zhun)確的說,還(huan)應乘上電機效率,一(yi)般(ban)為0.9。我(wo)們常見的三相電機額(e)定(ding)電壓(ya)(U)是380v。功率因數(COSφ)一(yi)般(ban)是0.85,電機銘牌上有(you)標(biao)注(zhu)。

10KW的三相電(dian)機額(e)定電(dian)流(liu)的具體(ti)算法:

I=10000÷(380×1.73×0.85×0.9)=19.8A。

 

Part.2

測(ce)知電力變壓器二(er)次側電流,求算其所載負荷容(rong)量

口訣:

已知配變(bian)二次壓,測得電流求千瓦(wa)。

電(dian)壓等級四百(bai)伏,一安零點六千瓦。

電壓(ya)等級三千伏(fu),一安(an)四點五千瓦。

電壓等級六(liu)千伏,一安整(zheng)數九千瓦。

電壓等(deng)級十千伏,一安一十五千瓦。

電壓等級三萬五,一(yi)安五十(shi)五千瓦(wa)。

 

Part.3

測知白熾燈照明(ming)線(xian)路電(dian)流,求算其負荷容量(liang)

口訣:

照明(ming)電壓二(er)百二(er),一安二(er)百二(er)十瓦。

 

不論供電(dian)(dian)(dian)還是配電(dian)(dian)(dian)線(xian)(xian)路,只要用鉗型(xing)電(dian)(dian)(dian)流(liu)(liu)表測得某相線(xian)(xian)電(dian)(dian)(dian)流(liu)(liu)值,然(ran)后乘以220系數,積(ji)數就是該相線(xian)(xian)所載負荷(he)容(rong)量(liang)(liang)。測電(dian)(dian)(dian)流(liu)(liu)求容(rong)量(liang)(liang)數,可幫助電(dian)(dian)(dian)工(gong)(gong)迅速(su)調整照明干線(xian)(xian)三相負荷(he)容(rong)量(liang)(liang)不平衡(heng)問(wen)題(ti),可幫助電(dian)(dian)(dian)工(gong)(gong)分(fen)析配電(dian)(dian)(dian)箱內(nei)保護熔(rong)體(ti)經(jing)常熔(rong)斷的原因(yin),配電(dian)(dian)(dian)導線(xian)(xian)發熱的原因(yin)等等。

 

Part.4

測知無(wu)銘(ming)牌380V單相(xiang)焊接變壓器的空(kong)載電流,求算額定容量

口訣:

三百八焊機(ji)容量,空(kong)載電流乘(cheng)以(yi)五。

 

變壓器的(de)(de)空(kong)載電(dian)流(liu)(liu)一般約為額(e)定電(dian)流(liu)(liu)的(de)(de)6%~8%(國家(jia)規定空(kong)載電(dian)流(liu)(liu)不應大于額(e)定電(dian)流(liu)(liu)的(de)(de)10%)。這就是口(kou)訣和公式的(de)(de)理論依(yi)據。

 

Part.5

已知380V三相電動機容量,求其過載保護熱繼電器元件額定電流和整定電流

口訣:

電(dian)機過載的(de)保護,熱(re)繼(ji)電(dian)器熱(re)元件;

號流容量兩倍半(ban),兩倍千瓦(wa)數整定。

 

熱(re)(re)元(yuan)件整定電(dian)流(liu)(liu)按(an)“兩倍(bei)千瓦數整定”;熱(re)(re)元(yuan)件額(e)定電(dian)流(liu)(liu)按(an)“號(hao)(hao)流(liu)(liu)容(rong)量(liang)兩倍(bei)半”算選;熱(re)(re)繼(ji)電(dian)器的型號(hao)(hao)規格,即(ji)其額(e)定電(dian)流(liu)(liu)值(zhi)應大(da)于等于熱(re)(re)元(yuan)件額(e)定電(dian)流(liu)(liu)值(zhi)。

 

Part.6

已知380V三相電動機容量,求(qiu)其遠(yuan)控交流接觸器額定電流等級

口訣:

遠控電機接觸(chu)器,兩倍(bei)容(rong)量靠等級(ji);

步繁(fan)起(qi)動正反轉,靠級(ji)基礎(chu)升一級(ji)。

 

Part.7

已知小型380V三相籠型電動機容量,求其供電設備最小容量、負荷開關、保護熔體電流值

口訣:

直(zhi)接起動(dong)電動(dong)機,容量(liang)不超十千瓦(wa);

六倍(bei)千(qian)瓦(wa)選(xuan)開(kai)關,五倍(bei)千(qian)瓦(wa)配熔體。

供(gong)電設備千伏安,需大三倍千瓦(wa)數。

 

說明:

口訣所述的(de)(de)(de)直接(jie)起(qi)(qi)動(dong)(dong)(dong)(dong)的(de)(de)(de)電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji),是小(xiao)型380V鼠籠型三相電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji),電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji)起(qi)(qi)動(dong)(dong)(dong)(dong)電(dian)流(liu)很大,一般(ban)是額定電(dian)流(liu)的(de)(de)(de)4~7倍。用(yong)負荷(he)開(kai)(kai)(kai)(kai)(kai)關(guan)直接(jie)起(qi)(qi)動(dong)(dong)(dong)(dong)的(de)(de)(de)電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji)容(rong)量(liang)最大不應超過10kW,一般(ban)以4.5kW以下為宜(yi),且開(kai)(kai)(kai)(kai)(kai)啟式負荷(he)開(kai)(kai)(kai)(kai)(kai)關(guan)(膠蓋瓷底隔離開(kai)(kai)(kai)(kai)(kai)關(guan))一般(ban)用(yong)于5.5kW及以下的(de)(de)(de)小(xiao)容(rong)量(liang)電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji)作(zuo)不頻繁的(de)(de)(de)直接(jie)起(qi)(qi)動(dong)(dong)(dong)(dong);封閉式負荷(he)開(kai)(kai)(kai)(kai)(kai)關(guan)(鐵(tie)殼開(kai)(kai)(kai)(kai)(kai)關(guan))一般(ban)用(yong)于10kW以下的(de)(de)(de)電(dian)動(dong)(dong)(dong)(dong)機(ji)(ji)作(zuo)不頻繁的(de)(de)(de)直接(jie)起(qi)(qi)動(dong)(dong)(dong)(dong)。

兩(liang)者均需(xu)有熔體作短(duan)路保護,還有電動機(ji)功率不大于供電變壓(ya)器容(rong)量的(de)(de)30%。總之(zhi),切記(ji)電動機(ji)用負荷開(kai)關直接起動是(shi)有條件的(de)(de)!

 

Part.8

電機起動星三角,起動時間好整定

口訣:

容量(liang)開方乘以二(er),積數加四單位秒(miao)。

電(dian)機起動星三(san)角,過載保護熱(re)元件;

整定電流相電流,容量(liang)乘八除(chu)以(yi)七。

 

時間(jian)繼(ji)電(dian)器(qi)調(diao)整時,暫不接入電(dian)動機進行操作(zuo),試(shi)驗(yan)(yan)(yan)時間(jian)繼(ji)電(dian)器(qi)的動作(zuo)時間(jian)是否能與所控制的電(dian)動機的起動時間(jian)一(yi)致。如(ru)果不一(yi)致,就應(ying)再微(wei)調(diao)時間(jian)繼(ji)電(dian)器(qi)的動作(zuo)時間(jian),再進行試(shi)驗(yan)(yan)(yan)。但兩(liang)次試(shi)驗(yan)(yan)(yan)的間(jian)隔至(zhi)少(shao)要(yao)在90s以上(shang),以保證雙(shuang)金屬時間(jian)繼(ji)電(dian)器(qi)自動復位(wei)。

 

Part.9

已知籠型電動機容量,求算控制其的斷路器脫扣器整定電流

口訣:

斷路器(qi)的脫扣器(qi),整定電流容量(liang)倍;

瞬時一般(ban)是二(er)十,較小電機(ji)二(er)十四;

延(yan)時脫扣三倍(bei)半,熱脫扣器整兩(liang)倍(bei)。

 

斷路器的(de)(de)脫扣器整定(ding)電(dian)(dian)流值計(ji)算(suan)是電(dian)(dian)工常遇(yu)到的(de)(de)問題(ti),口訣給出了整定(ding)電(dian)(dian)流值和所控制(zhi)的(de)(de)籠型電(dian)(dian)動機容(rong)量(liang)千(qian)瓦(wa)數之間的(de)(de)倍(bei)數關系。

 

“延(yan)時(shi)(shi)脫(tuo)扣(kou)三倍(bei)(bei)半,熱脫(tuo)扣(kou)器(qi)整兩(liang)倍(bei)(bei)”說的(de)(de)是作為(wei)過載保護的(de)(de)自動斷路器(qi),其延(yan)時(shi)(shi)脫(tuo)扣(kou)器(qi)的(de)(de)電(dian)(dian)(dian)流整定(ding)值(zhi)可按所(suo)控制電(dian)(dian)(dian)動機(ji)額定(ding)電(dian)(dian)(dian)流的(de)(de)1.7倍(bei)(bei)選(xuan)擇(ze),即(ji)3.5倍(bei)(bei)千(qian)瓦(wa)數選(xuan)擇(ze)。熱脫(tuo)扣(kou)器(qi)電(dian)(dian)(dian)流整定(ding)值(zhi),應等于或略大(da)于電(dian)(dian)(dian)動機(ji)的(de)(de)額定(ding)電(dian)(dian)(dian)流,即(ji)按電(dian)(dian)(dian)動機(ji)容量千(qian)瓦(wa)數的(de)(de)2倍(bei)(bei)選(xuan)擇(ze)。

 

Part.10

已知異步電動機容量,求算其空載電流

口訣:

電(dian)動機空載電(dian)流,容量八折(zhe)左(zuo)右求(qiu);

新(xin)大極數少六(liu)折,舊小極多千瓦(wa)數。

 

一般(ban)小(xiao)型(xing)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)約為額(e)定電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)的(de)(de)(de)30%~70%,大(da)中(zhong)型(xing)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)約為額(e)定電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)的(de)(de)(de)20%~40%。具體到某臺(tai)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)是多少(shao)(shao),在(zai)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)銘牌或產(chan)品(pin)說明書上,一般(ban)不(bu)(bu)標(biao)注。可電(dian)(dian)(dian)(dian)(dian)工常需知道此數值是多少(shao)(shao),以(yi)此數值來(lai)判(pan)斷(duan)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)修(xiu)理的(de)(de)(de)質量(liang)(liang)(liang)好壞,能否使(shi)(shi)用。它符(fu)合“電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)一般(ban)是其額(e)定電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)的(de)(de)(de)1/3”。同時它符(fu)合實踐經驗(yan):“電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu),不(bu)(bu)超過容(rong)(rong)量(liang)(liang)(liang)千(qian)瓦數便(bian)可使(shi)(shi)用”的(de)(de)(de)原則(指檢修(xiu)后的(de)(de)(de)舊(jiu)式、小(xiao)容(rong)(rong)量(liang)(liang)(liang)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji))。口訣“容(rong)(rong)量(liang)(liang)(liang)八折(zhe)左(zuo)右求”是指一般(ban)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)值是電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)額(e)定容(rong)(rong)量(liang)(liang)(liang)千(qian)瓦數的(de)(de)(de)0.8倍(bei)左(zuo)右。中(zhong)型(xing)、4或6極(ji)(ji)電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)的(de)(de)(de)空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu),就是電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji)容(rong)(rong)量(liang)(liang)(liang)千(qian)瓦數的(de)(de)(de)0.8倍(bei);新系列,大(da)容(rong)(rong)量(liang)(liang)(liang),極(ji)(ji)數偏(pian)小(xiao)的(de)(de)(de)2級電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji),其空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)計(ji)(ji)算按“新大(da)極(ji)(ji)數少(shao)(shao)六折(zhe)”;對舊(jiu)的(de)(de)(de)、老式系列、較小(xiao)容(rong)(rong)量(liang)(liang)(liang),極(ji)(ji)數偏(pian)大(da)的(de)(de)(de)8極(ji)(ji)以(yi)上電(dian)(dian)(dian)(dian)(dian)動(dong)(dong)(dong)機(ji),其空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu),按“是小(xiao)極(ji)(ji)多千(qian)瓦數”計(ji)(ji)算,即空(kong)(kong)(kong)(kong)載(zai)電(dian)(dian)(dian)(dian)(dian)流(liu)(liu)值近似等于容(rong)(rong)量(liang)(liang)(liang)千(qian)瓦數,但一般(ban)是小(xiao)于千(qian)瓦數。

 

Part.11

已知電力變壓器容量,求算其二次側(0.4kV)出線自動斷路器瞬時脫扣器整定電流值

口訣:

配變二次側供電,最好配用斷路器(qi);

瞬時(shi)脫扣(kou)整定(ding)值,三倍容(rong)量千伏安。

 

Part.12

判(pan)斷同(tong)相與異相

訣:

判斷兩線相同異,兩手(shou)各持一支筆(bi),

兩腳與地相絕(jue)緣,兩筆(bi)各觸一(yi)要線,

用(yong)眼(yan)觀看(kan)一(yi)支筆,不亮(liang)同相亮(liang)為異(yi)。

 

此項測試時,切記兩腳與地(di)必須(xu)絕(jue)緣。因為我國大(da)部分是380/220V供電,且變壓(ya)器普遍采用中性點(dian)直接接地(di),所以做測試時,人(ren)體與大(da)地(di)之(zhi)間一定要(yao)絕(jue)緣,避免構成回路,以免誤判斷;測試時,兩筆亮(liang)與不(bu)亮(liang)顯示一樣,故只(zhi)看(kan)一支則可。

 

Part.13

判斷直流電正負極

口訣:

電筆判斷正負(fu)極,觀察氛管要心(xin)細,

前端(duan)明亮是負極(ji),后端(duan)明亮為正極(ji)。

 

Part.14

判斷交流(liu)電(dian)與直流(liu)電(dian)

口訣:

電筆判斷交直流,交流明亮直流暗,

交流氛管通(tong)身亮,直流氖(nai)管亮一端。

 

Part.15

判斷直流電源有無接地,正負極接地的區別

口訣:

變電所(suo)直流系數,電筆觸及不發亮;

若亮靠近筆尖端,正極有(you)接(jie)地(di)故(gu)障;

若(ruo)亮靠近手指端(duan),接地故障在負極(ji)。

 

Part.16

銅芯電纜導線安全載流量計算

口訣:

10下五,100上(shang)二,16、25四,35、50三,70、95兩倍半。

穿管、溫度八、九折,裸線加(jia)一半。銅線升級算。

 

口訣中(zhong)的(de)阿拉伯數字與倍數的(de)排列關系如下:

對于(yu)1.5、2.5、4、6、10mm2的導(dao)線可將(jiang)其截面積數乘以5倍。

對于(yu)16、25mm2的導(dao)線可將其截面積數乘以4倍。

對于35、50mm2的(de)導線(xian)可將其截面(mian)積數(shu)乘以3倍。

對于(yu)70、95mm2的導線可將其截面積數乘(cheng)以2.5倍。

對于120、150、185mm2的導線可(ke)將(jiang)其截(jie)面積(ji)數乘以2倍。

銅線面積升一級(ji)算(suan)。

 

Part.17

斷路器的選(xuan)擇

斷(duan)路器(qi)由于(yu)(yu)是進行斷(duan)路保護因此(ci)可以選(xuan)擇(ze)大于(yu)(yu)電(dian)(dian)(dian)機額(e)定電(dian)(dian)(dian)流(liu),通常為(wei)電(dian)(dian)(dian)機額(e)定電(dian)(dian)(dian)流(liu)1.2倍,保守為(wei)1.6倍,熱繼電(dian)(dian)(dian)器(qi)通常選(xuan)擇(ze)了0.95~1.05倍電(dian)(dian)(dian)機額(e)定電(dian)(dian)(dian)流(liu),個人傾向于(yu)(yu)1倍。

 

Part.18

交流接(jie)觸(chu)器的選(xuan)擇

(1)持續運行的設備。接(jie)觸器按67-75%算,即100A的交流接(jie)觸器,只能控制最大額定電流是(shi)67-75A以下的設備.

(2)間(jian)斷運行(xing)的設備(bei)。接(jie)觸器按80%算,即100A的交流(liu)接(jie)觸器,只(zhi)能控制(zhi)最大額定(ding)電(dian)流(liu)是80A以(yi)下的設備(bei).

(3)反復短(duan)時工(gong)作的設備。接觸器按116-120%算(suan),即100A的交流接觸器,只能(neng)控制最(zui)大額定電流是(shi)116-120A以下的設備。

還要考慮工作環境(jing)和接觸器的結構形(xing)式。

 

Part.19

電焊機

1)380V電(dian)焊(han)機I=1000S/U=1000S/380=2.63S

220V電焊機I=1000S/U=1000S/220=4.55S可(ke)總(zong)結為(wei):

三(san)百八的電焊機,二點(dian)六(liu)倍千伏安(an);

二(er)百二(er)的(de)電焊機,四點五倍千伏(fu)安。

 

2)電(dian)焊(han)(han)機通常分為(wei)電(dian)弧焊(han)(han)和電(dian)阻焊(han)(han)兩(liang)大類,其中電(dian)阻焊(han)(han)(對(dui)焊(han)(han)、點焊(han)(han)、縫焊(han)(han)等)接用的時(shi)間(jian)更短(duan)些。上面說過,對(dui)它(ta)們配線可以小一些,具(ju)體作法是:

先將容量(liang)改變(降低),可按“孤焊(han)八(ba)折,阻焊(han)半”的口訣進行。即電弧焊(han)機類將容量(liang)打八(ba)折,電阻焊(han)機類打對折(乘0.5),然(ran)后再按這(zhe)改變了的容量(liang)進行配電。

 

(1)30千伏安(an)交流弧焊機,按(an)“孤焊八(ba)折”,則30×0.8=24,即配(pei)電時容量可改(gai)為24千伏安(an)。當(dang)接用380伏單(dan)相(xiang)時,可按(an)24×2.5=60安(an)配(pei)電。

(2)30千(qian)伏安點焊機,按“阻焊半”,則(ze)30×0.5=15,即(ji)可按15千(qian)伏安配電。

當為380伏單(dan)相(xiang)時,按15×2.5=37.5A配(pei)電。

 

Part.20

星三角啟動的電機接觸器選型

1)電(dian)(dian)機銘牌上(shang)所(suo)標額(e)定電(dian)(dian)流(liu)指的是線(xian)電(dian)(dian)流(liu)。

2)電(dian)機銘牌上(shang)的額定功率(lv)指(zhi)的是在(zai)規定接法的條(tiao)件(jian)下(xia)的功率(lv)。

3)采用星三角啟動的電機,轉換后兩個在(zai)工作(zuo)的接(jie)觸器只承受(shou)0.58倍的線電流。

4)規定采用三角(jiao)形接法的電(dian)機(ji)(ji),改(gai)成星形接法時電(dian)機(ji)(ji)功率會大幅下降。此時線電(dian)流也下降到原來的0.58倍。

 

本文來源于網絡(luo),版權歸原作者所有。但因(yin)轉載眾多,無法確(que)認原作者,故僅標明轉載來源。

 

 